Troubleshooting "How To" Manual for the SMS
The main troubleshooting methods all stem from the alarm control page
in the control system computer. This document will serve to define
what actions need to be taken when a certain alarm goes off on the
"Alarm Control" panel on LookoutDirect running on the SMS control
system computer. The shift crew will not have access to the Hall
during beam time therefore this document is limited to what the crew
can do remotely with the control system.
The control system is on the computer g0-sms.jlab.org. This system
can be accessed remotely using virtual network computing
(VNC) from a Java-enabled web browser. Go to http://g0-sms.jlab.org:5800
and use the generic G0 password to log on. A special VNC viewer
client can be used instead.
As a general rule, a shift crew should not push any buttons or
close/reboot any software without consulting a magnet expert
first. The on-call magnet expert can always be reached via pager at
number 584-5574.
The exception to this rule would be the buttons needed to navigate
between Panels. (e.g. Main, Alarm Control, CDHXR, Interlocks, etc.
located toward the top of the control system screen).
When an alarm goes off, and the problem has been solved, the alarm can
be silenced by going to: Alarms (pull down menu) -> Acknowledge
All. Then go to the Alarm Control page and press the Reset button for
at least one second.
A quick way to find the relevant troubleshooting section is to ctrl-f (alt-f on unix/linux) and search for the alarm number
1212 H2O Temperature A Low
1222 H2O Temperature B Low
This is the water cooling for the A and B leads. A low temperature
warning indicates that the water in the leads near the top of the
magnet may be in danger of freezing.
- Go to the Water page and observe the water temperatures in the
appropriate strip chart.
- If the temperature drop was not a temporary event, then notify the
on call magnet expert.
1311 H2O Flow A Low
1321 H2O Flow B Low
1331 H2O Flow Jumper Low
1341 H2O Flow PS Low
This shows the status of the water flow through the Power supply, A and B leadds, and the Jumper leads. When the flow stops or is reduced below a certain setpoint, there is danger of overheating.
- This alarm should cause a slow dump of the current in the
magnet. Verify that the slow dump has occurred by going to the Power
Supply page and watching the current ramp down.
- Go to the Water page and observe the water flows in the
appropriate strip chart.
- Notify the magnet expert.
2111 LHe Inlet Pressure Low
If LHe Inlet Pressure is too low, this could mean that there is
reduced LHe flow going into the magnet. In time, this could cause the
He in the reservoir to be consumed and the coil temperatures to
rise.
- Go to the LHe Level page and observe the He inlet pressure in the
appropriate strip-chart.
- If the He inlet pressure does not rise back to its original value
within a couple of minutes or continues in a steep decline,
then notify the on-call magnet expert.
2131 LHe Reservoir Pressure Low.
2140 LHe Reservoir Pressure High.
- Go to the LHe Level page and observe the He reservoir pressure in the
appropriate strip-chart.
- If the He reservoir pressure does not return to its original value
within a couple of minutes or continues in a steep decline/incline,
then notify the on-call magnet expert.
2211 CDHXR Temperature High.
Once we are cooling with LHe near 4.5 K, we won't be using the Cooldown Heat Exchanger. This is used when we are cooling from 300K to ~100K.
- Ignore alarm, but make sure the magnet expert gets notified
during normal working hours.
2221 LHe Inlet Temperature High.
This, along with "2111 LHe Inlet Pressure Low" could mean trouble with
the LHe flow.
- Go to the LHe Level page and observe the He inlet temperature in the
appropriate strip-chart.
- If the He inlet pressure does not rise back to its original value
within a couple of minutes or continues in a steep decline,
then notify the on-call magnet expert.
2311 VCL A Flow Low
2321 VCL B Flow Low
- Go to the Lead page and observe the lead flows in the appropriate
strip-chart.
- If the lead flow does not immediately rise to its original value,
then notify the on-call magnet expert.
2401 LHe Level Low (Yellow)
The reduced level of LHe that causes this alarm could be the sign of a
problem somewhere in the cryogenic system or it could be due to a
normal fluctuation of the PID loop.
- Go to the LHe Level page and observe the LHe level in the
appropriate strip-chart.
- Monitor the level for several minutes.
- If the level does not increase above the threshold, then notify
the on-call magnet expert.
2402 LHe Level Low (Orange)
Alarm 2401 should have signalled prior to this alarm. If the liquid
level gets this low, then there is almost certainly a problem in the
cryogenic system or the ESR.
- This alarm should cause a slow dump of the current in the
magnet. Verify that the slow dump has occurred by going to the Power
Supply page and watching the current ramp down.
- Go to the LHe Level page and observe the LHe level in the
appropriate strip chart.
- Notify the magnet expert.
3131 LN2 Reservoir Pressure Low
3140 LN2 Reservoir Pressure High
This alarm could indicate a problem in the liquid nitrogen circuit or
it could arise from natural fluctuations in the PID control loop.
- Go to the LN2 Level page and observe the LN2 reservoir pressure
in the appropriate strip chart.
- If the LN2 reservoir pressure does not return to its original
value within several minutes, then notify the on-call magnet
expert.
3211 LN2 Bayonet Temperature High
This can happen if the JT5 valve position is closed down (not
necessarily to 0) As the valve is closed, the LN2 bayonet begins to
warm up since there is reduced LN2 flow. This happens occasionally as
the PID loop needs to close the valve in order to reduce the LN2
reservoir level.
- Go to the LN2 Level page and observe the LN2 bayonet temperature
in the appropriate strip chart.
- If the LN2 bayonet temperature does not start to drop within a
few minutes, then notify the on-call magnet expert.
3400 LN2 Level Low
- Go to the LN2 Level page and observe the LN2 level
in the appropriate strip chart.
- If the LN2 level does not begin to rise within a
few minutes, then notify the on-call magnet expert.
4111 Vessel TC Pressure High
4121 Vessel CC Pressure High
4211 Cryobox/LN2 Bayonet Pressure High
- Go to the Vacuum page and observe the vacuum in the appropriate
strip chart.
- If the vacuum does not drop to normal levels within a few
minutes, then notify the on-call magnet expert.
25 Voltage Transition Lead A alarm (Yellow)
28 Voltage Transition Lead B alarm (Yellow)
These alarms occur if the voltage measured in the transition leads is
slightly higher than the nominal value; indicating a potential quench
situation.
- This alarm should cause a slow dump of the current in the
magnet. Verify that the slow dump has occurred by going to the Power
Supply page and watching the current ramp down.
- Go to the Quench Protection page and observe the lead voltage in
the appropriate strip-chart.
- Notify the on-call magnet expert.
26 Voltage Transition Lead A alarm (Orange)
29 Voltage Transition Lead B alarm (Orange)
31 - 38 Voltage Coil A-H Quench
This alarm indicates that one or more of the coils or transition leads
has gone normal, or quenched.
- This alarm should cause a fast dump of the current in the
magnet. Verify that the fast dump has occurred by going to the Power
Supply page and checking the value of the current.
- If the current has not gone to zero within a few seconds and the
dump switch is still closed (as noted on the Power Supply page), then
push the Open Dump Switch button to trigger a fast dump.
- Notify the on-call magnet expert.
8210 Temperatures Not Updating
This occurs occasionally with the temperature monitoring (Tempmon)
software installed on the control system computer. Sometimes, the USB
<-> Serial converter that the Temperature readings are fed through can
stop. Thus the remedy is to reboot the USB <-> Serial converter.
This process has been automated so generally no action will need to be
taken.
- Acknowledge the alarm and reset as normal.
- If alarm occurs again within five minutes, then notify the on-call
magnet expert.